Standard: IEC60947-2
Poles: 3P
Frame Current: 800A
Rated Current: 630,700,800A
Rated voltage: 800/1000/1140V
Rated insulation voltage: 1250V
Rated impulse withstand voltage: 12kV
Trip unit technology: Thermal-magnetic
Ambient Temperature: -25...+40 ºC
EKM6-800H Moulded Case Circuit Breaker (MCCB) offers an 800A frame rating with currents from 630A to 800A, ensuring reliable protection for high-power systems.
Designed for peak performance, it provides short-circuit protection with a breaking capacity of 50kA at 800V, 20kA at 1000V, and 15kA at 1140V, along with a 1250V insulation voltage for dependable operation in high-voltage environments.
Compliant with IEC60947-2 standards, this 3-pole breaker uses advanced thermal-magnetic trip technology, functioning efficiently across -25°C to +40°C. With a mechanical lifespan of 20,000 operations and electrical durability of 1,500 operations, the EKM6-800H is ideal for industrial facilities, power plants, and large-scale manufacturing, where maximum reliability and current capacity are critical.
Model |
EKM6-800H |
|
Ampere frame (Inm) |
800A |
|
Rated current (In) |
630,700,800A |
|
Rated insulation voltage (Ui) |
1250V |
|
Rated impulse withstand voltage (Uimp) |
12kV |
|
Rated operational voltage (Ue) |
800V, 1000V, 1140V |
|
Rated ultimate short-circuit Breaking capacity (Icu) kA |
800V |
50 |
|
1000V |
20 |
|
1140V |
15 |
Rated service short-circuit breaking capacity (Ics) kA |
800V |
37.5 |
|
1000V |
15 |
|
1140V |
15 |
Isolation function |
Available |
|
Utilization category |
Cat.A |
|
Type of trip unit |
Thermal-Magnetic |
|
Mechanical life (Times) |
20000 |
|
Electrical life (Times) |
1500 |
GET A QUOTE