Standard: IEC60947-2
Poles: 2P/3P
Frame Current: 400A
Rated Current: 250,315,350,400A
Rated voltage: 250,500,750,1000,1250,1500 VDC
Rated insulation voltage: 1500V
Rated impulse withstand voltage: 12kV
Trip unit technology: Thermal-magnetic
Ambient Temperature: -25...+50 ºC
Application: photovoltaic / UPS / battery / data center etc.
EKM6DC-400 DC Molded Case Circuit Breaker is designed for high-voltage DC systems, supporting rated currents from 250A to 400A and voltages up to 1500V. Its robust design ensures reliable protection against overloads and short circuits, making it suitable for solar PV, wind power, and battery storage systems. With compliance to IEC60947-2 standards, it offers excellent insulation performance and breaking capacity for demanding applications.
Model |
EKM6DC-400 |
EKM6DC-400V |
|||
Ampere frame (Inm) |
400A |
400A |
|||
Rated current (In) |
250,315,350,400 |
250,315,350,400 |
|||
Rated impulse withstand voltage (Uimp) |
12kV |
||||
Rated operational voltage (Ue) |
2P |
250,500,750,1000,1250,1500 VDC |
|||
|
3P |
1000,1500 VDC |
|||
Rated ultimate short-circuit Breaking capacity (Icu) kA |
2P |
DC250V |
25 |
70 |
|
|
|
DC500V |
25 |
70 |
|
|
|
DC750V |
15 |
50 |
|
|
|
DC1000V |
15 |
50 |
|
|
|
DC1250V |
/ |
20 |
|
|
|
DC1500V |
10 |
20 |
|
|
3P |
DC1000V |
30 |
/ |
|
|
|
DC1500V |
25 |
/ |
|
Rated service short-circuit breaking capacity (Ics) kA |
100% Icu |
||||
Isolation function |
Available |
||||
Utilization category |
Cat.A |
||||
Type of trip unit |
Thermal-Magnetic |
||||
Mechanical life (Times) |
15000 |
||||
Electrical life (Times) |
1000 |
800 |
|||
Arcing distance (mm) |
≤100 |
GET A QUOTE